Transformer performance

Transformer performance

Performance transformer

\[ \rho= 100 · \frac{S_{CARGA} · cos φ}{S_{CARGA} · cos φ + P_{VACÍO} + Pll · \left(\frac{S_{LOAD}}{Sn}\right)^2 } \]

· ρ: Transformer performance, %

· Sload: Transformer load, kVA

· NLL: No-load losses, kW

· LL: Load losses, kW

· Sn: Apparent power, kVA

Voltage drop

\[ Er = 100 · \frac{P_{LOAD}}{S} \] \[ Ex = \sqrt{Usc^2 - Er^2} \] \[ E = \frac{_{S_{LOAD}}}{Sn} · (Er · cos φ ± Ex · sen φ) \]

· E: Voltage drop, V

· Sload: Transformer load, kVA

· Sn: Apparent power, kVA

· Usc: Shot-circuit transformer, %

· Er: Drop resistance, %

· Ex: Drop reactance, %