Earth fault current
Earth fault current
\[ I_f = c · \frac{ \sqrt{3} · U · (ω · Ca · La + ω · Cc · Lc)}{ \sqrt{1 + (ω · Ca · La + ω · Cc · Lc)^2 · (3 · Rg)^2 }} \]· IF: Earth fault current, A
· c: Voltage factor c = 1,10
· U: Voltage between phases, kV
· Ca: Overhead line zero sequence capacitance, F/km
· La: Total length of overhead lines departing from the substation, km
· Ca: Underground line zero sequence capacitance, F/km
· La: Total length of subway lines departing from substation, km
· ω: Current pulsation (2·π·fnet), Hz
· Rg: Grounding resistance, Ω
Neutral isolated
\[ I_f = c · \frac{U}{\sqrt{3} · \sqrt{(Rn + Rg)^2 + (Xn)^2 }} \]· If: Earth fault current, A
· c: Voltage factor c = 1,10
· U: Voltage between phases, kV
· Rn: Grounding resistance of the network neutral, Ω
· Rg: Grounding resistance, Ω
· Xn: Grounding reactance of the network neutral, Ω